Home > Product List > Pressure Transmitter > Pressure  Transmitter  (For  Refrigeration  Compressor  and  Humidifier)

Pressure Transmitter (For Refrigeration Compressor and Humidifier)

Model/Item No.: PT-RCH1100
Brand: ATLANTIS
Sales Method: Export, Manufacture
Payment Terms: T/T,L/C

Product Specifications:

Pressure Transmitter (For Refrigeration Compressor and Humidifier)
Model: PT-RCH1100
Introduction
PT-RCH 1100 pressure transmitter mainly used in refrigeration compressors and humidifiers. It apply to measure the pressure of refrigerants (before/after energy exchange) or humidifiers, the measured pressure value will transmit to control unit to control refrigeration compressors and humidifiers working status accordingly.
 
Features
OEM service
Accuracy ±1.0% F.S.
Transmit measured pressure value to refrigeration compressors or humidifiers’ control unit
 
Main Specifications
▼Pressure connection
7/16-20UNF / 9/16-20UNF
▼Sealing 
O-ring sealed
Material: CR (Neoprene) / 
HNBR (Hydrogenated Nitrile)
▼Electrical connection
Packard
▼Pressure range
-1.0…0~2…50bar
▼Pressure type
Gauge pressure
▼Applicable refrigerant
CR O-ring sealing: 
R12, R22, R134a, R404A, R407C, R410A, R507
HNBR O-ring sealing:
R134a, R404A, R407C, R410A, R507
▼Applicable fluid
Gas and liquid that compatible with SS304 and ceramic
▼Medium temperature
-20 to 120℃
▼Protection level
IP 65
 
Other Specifications
▼Housing material
SS 304
▼Supply voltage
10~30VDC (Two-wire) / 
5VDC (Three-wire)
▼Output signal
4~20 mA (Two-wire)
0.5 ~ 2.5…4.5 VDC (Three-wire)
▼Measuring elements
Ceramic capacitive pressure sensor
▼Response time
10ms
▼Accuracy
±1.0% F.S.
▼Operating pressure
Overpressure: 1.5* full scale
Burst pressure: 2* full scale
▼Electromagnetic field radiation
±10V/m
▼Static electricity
Air discharge: ±8kV 
Contact discharge: ±4kV
▼Other requests (Option)
Third party notarized documents
Inspection report (issued by Re-Atlantis)
Tag
 

Supplementary Product Illustration:

DM.pdf

Competitive Advantages:

Well and High Quality Control,Competitive Prices,OEM Accepted

Keywords:

Pressure Transmitter (For Refrigeration Compressor and Humidifier),Pressure Transmitter,Transmitter,Refrigeration Compressor,Humidifier,For Refrigeration Compressor,For Humidifier